Look in LIEBERT_GP_REG.MIB and LIEBERT_GP_ENV.MIB 2 is identity SNMPv2-SMI::enterprises.476.1.42.2.1.1.0 = STRING: "Liebert Corporation" SNMPv2-SMI::enterprises.476.1.42.2.1.2.0 = STRING: "IntelliSlot Web/485 Card" SNMPv2-SMI::enterprises.476.1.42.2.1.3.0 = STRING: "3.120.7" SNMPv2-SMI::enterprises.476.1.42.2.1.4.0 = STRING: "416791G407T2007AUG170180" SNMPv2-SMI::enterprises.476.1.42.2.1.5.0 = STRING: "OCWEB-ADPT" SNMPv2-SMI::enterprises.476.1.42.2.4.2.1.1.1 = INTEGER: 1 SNMPv2-SMI::enterprises.476.1.42.2.4.2.1.2.1 = OID: SNMPv2-SMI::enterprises.476.1.42.4.3.1 SNMPv2-SMI::enterprises.476.1.42.2.4.2.1.3.1 = STRING: "Liebert Corporation" SNMPv2-SMI::enterprises.476.1.42.2.4.2.1.4.1 = STRING: "Advanced Microprocessor Control" SNMPv2-SMI::enterprises.476.1.42.2.5.1.0 = INTEGER: 0 3 is conditions (alarms?) 3.2.2 is starting a table, but have "0" entries here... SNMPv2-SMI::enterprises.476.1.42.3.2.2.0 = Gauge32: 0 3.4 is Environmental 3.4.1 is Temperature 3.4.1.2 is Fahrenheit the temp set point SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.1.0 = INTEGER: 78 temp variance in tenths SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.2.0 = INTEGER: 20 begins a table SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.3.1.1.1 = Gauge32: 1 SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.3.1.2.1 = OID: SNMPv2-SMI::enterprises.476.1.42.3.4.1.1.1 measured temp SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.3.1.3.1 = INTEGER: 77 high alarm SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.3.1.4.1 = INTEGER: 90 low alarm SNMPv2-SMI::enterprises.476.1.42.3.4.1.2.3.1.5.1 = INTEGER: 55 3.4.1.3 is Celsius SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.1.0 = INTEGER: 25 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.2.0 = INTEGER: 11 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.3.1.1.1 = Gauge32: 1 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.3.1.2.1 = OID: SNMPv2-SMI::enterprises.476.1.42.3.4.1.1.1 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.3.1.3.1 = INTEGER: 25 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.3.1.4.1 = INTEGER: 32 SNMPv2-SMI::enterprises.476.1.42.3.4.1.3.3.1.5.1 = INTEGER: 12 3.4.2.2 is Relative Humidity setpoint SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.1.0 = INTEGER: 40 range SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.2.0 = INTEGER: 3 begins a table SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.3.1.1.1 = Gauge32: 1 SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.3.1.2.1 = OID: SNMPv2-SMI::enterprises.476.1.42.3.4.2.1.1 measured SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.3.1.3.1 = INTEGER: 38 high alarm SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.3.1.4.1 = INTEGER: 60 low alarm SNMPv2-SMI::enterprises.476.1.42.3.4.2.2.3.1.5.1 = INTEGER: 17 3.4.3 is State (1=on 2=off 3=standby) system SNMPv2-SMI::enterprises.476.1.42.3.4.3.1.0 = INTEGER: 1 cooling SNMPv2-SMI::enterprises.476.1.42.3.4.3.2.0 = INTEGER: 1 heating SNMPv2-SMI::enterprises.476.1.42.3.4.3.3.0 = INTEGER: 2 humidifier SNMPv2-SMI::enterprises.476.1.42.3.4.3.4.0 = INTEGER: 1 dehumidifier SNMPv2-SMI::enterprises.476.1.42.3.4.3.5.0 = INTEGER: 2 econ-o-cycle SNMPv2-SMI::enterprises.476.1.42.3.4.3.6.0 = INTEGER: 2 (.8 indicates general alarm) % cooling stage SNMPv2-SMI::enterprises.476.1.42.3.4.3.9.0 = Gauge32: 25 % heating SNMPv2-SMI::enterprises.476.1.42.3.4.3.10.0 = Gauge32: 0 3.4.4 is Configuration (1=lockedout/disabled 2=notlockedout/enabled) reheat SNMPv2-SMI::enterprises.476.1.42.3.4.4.1.0 = INTEGER: 1 humidifier SNMPv2-SMI::enterprises.476.1.42.3.4.4.2.0 = INTEGER: 2 3.4.5 is Control shutdown SNMPv2-SMI::enterprises.476.1.42.3.4.5.1.0 = INTEGER: -1 start SNMPv2-SMI::enterprises.476.1.42.3.4.5.2.0 = INTEGER: -1 3.4.6 is operational time table comp 1 run hours SNMPv2-SMI::enterprises.476.1.42.3.4.6.1.0 = Gauge32: 15189 comp 2 run hours SNMPv2-SMI::enterprises.476.1.42.3.4.6.2.0 = Gauge32: 15621 main fan run hours SNMPv2-SMI::enterprises.476.1.42.3.4.6.3.0 = Gauge32: 22869 humidifier run hours SNMPv2-SMI::enterprises.476.1.42.3.4.6.4.0 = Gauge32: 13911 reheat 1 SNMPv2-SMI::enterprises.476.1.42.3.4.6.7.0 = Gauge32: 1288 reheat 2 SNMPv2-SMI::enterprises.476.1.42.3.4.6.8.0 = Gauge32: 1221 reheat 3 SNMPv2-SMI::enterprises.476.1.42.3.4.6.9.0 = Gauge32: 1255